Inverter vettoriale standard serie Delta MS300
PARAMETRI DEL PRODOTTO
- Compact and standard vector inverter with high functionality and reliability
- Supports induction and permanent magnet motors in open-loop control
- Built-in PLC, USB parameter copy, high-speed pulse input/output, and STO safety
- Multiple communication interfaces and tool-free terminal design for easy installation and maintenance
Descrizione
CARATTERISTICHE DEL PRODOTTO
The Delta MS300 Series is a compact and standard vector inverter designed for high functionality, reliability, and easy installation. It maximizes industrial resource efficiency, while optimized structure and tool-free terminals simplify maintenance and save installation time. The user-friendly interface allows easy parameter setting, and the built-in USB function enables fast parameter copying to enhance production efficiency.
MS300 supports both induction and permanent magnet motors in open-loop control. Standard models provide output frequencies from 0 to 599 Hz, while high-speed models reach up to 1500 Hz.
The series features a built-in 2k-step PLC for programmable operation, one 33kHz high-speed pulse input terminal (MI7), one 33kHz high-speed pulse output terminal (DFM), built-in or optional EMC filters, Torque Off (STO) safety certification (SIL2/PLd), and built-in brake choppers. New PCB coating meets IEC 60721-3-3 class 3C2, enhancing environmental resistance.
Additional features include a 5-digit high-brightness LED keypad with support for E/M/B extension cables to control panels, and multiple communication interfaces including PROFIBUS DP, Modbus TCP, EtherNet/IP, DeviceNet, and CANopen.
APPLICATION FIELDS
| Machine Tools | Textile Machines | Woodworking Machinery |
|---|---|---|
| Packaging Machines | Produzione elettronica | Fans |
| Water Pumps | Air Compressors |
SPECIFICHE TECNICHE
Single-phase 115V (Without Built-in EMC Filter)
| Frame | A | A | C | |
|---|---|---|---|---|
| Applicable Motor Power (kW) | 0.2 | 0.4 | 0.75 | |
| Applicable Motor Power (HP) | 1/4 | 1/2 | 1 | |
| Output – Heavy Load | Rated Output Current (A) | 1.6 | 2.5 | 4.8 |
| Output – Normal Load | Rated Output Current (A) | 1.8 | 2.7 | 5.5 |
| Carrier Frequency (kHz) | 2~15kHz (Preset: 4kHz) | |||
| Brake Chopper | Incorporato | |||
| DC Reactor | Optional | |||
| AC Reactor | Optional | |||
| Cooling Method | Natural Air Cooling | Natural Air Cooling | Forced Air Cooling | |
| Dimensions (W×H mm) | 68×128 | 68×128 | 87×157 | |
| Dimensions (D mm) | 96 | 125 | 152 |
| Frame | B | B | C | C | C | |
|---|---|---|---|---|---|---|
| Applicable Motor Power (kW) | 0.2 | 0.4 | 0.75 | 1.5 | 2.2 | |
| Applicable Motor Power (HP) | 1/4 | 1/2 | 1 | 2 | 3 | |
| Output – Heavy Load | Rated Output Current (A) | 1.6 | 2.8 | 4.8 | 7.5 | 11 |
| Output – Normal Load | Rated Output Current (A) | 1.8 | 3.2 | 5 | 8.5 | 12.5 |
| Carrier Frequency (kHz) | 2~15kHz (Preset: 4kHz) | |||||
| Brake Chopper | Incorporato | |||||
| DC Reactor | Optional | |||||
| AC Reactor | Optional | |||||
| Cooling Method | Natural Air Cooling | Natural Air Cooling | Forced Air Cooling | Forced Air Cooling | Forced Air Cooling | |
| Dimensions (W×H mm) | 72×142 | 72×142 | 87×157 | 87×157 | 87×157 | |
| Dimensions (D mm) | 159 | 159 | 179 | 179 | 179 |
Without Built-in EMC Filter
| Frame | A | A | B | C | |
|---|---|---|---|---|---|
| Cooling Method | Natural Air Cooling | Natural Air Cooling | Natural Air Cooling | Forced Air Cooling | |
| Dimensions (W×H mm) | 68×128 | 68×128 | 72×142 | 87×157 | |
| Dimensions (D mm) | 96 | 125 | 143 | 152 |
Three-phase 230V (Without Built-in EMC Filter)
| Frame | A | A | B | B | C | C | D | D | E | F | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Applicable Motor Power (kW) | 0.2 | 0.4 | 0.75 | 1.5 | 2.2 | 3.7/4 | 5.5 | 7.5 | 11 | 15 | |
| Applicable Motor Power (HP) | 1/4 | 1/2 | 1 | 2 | 3 | 5 | 7.5 | 10 | 15 | 20 | |
| Output – Heavy Load | Rated Output Current (A) | 1.6 | 2.8 | 4.8 | 7.5 | 11 | 17 | 25 | 33 | 49 | 65 |
| Output – Normal Load | Rated Output Current (A) | 1.8 | 3.2 | 5 | 8 | 12.5 | 19.5 | 27 | 36 | 51 | 69 |
| Carrier Frequency (kHz) | 2–15kHz (Preset: 4kHz) | ||||||||||
| Brake Chopper | Incorporato | ||||||||||
| DC Reactor | Optional | ||||||||||
| AC Reactor | Optional | ||||||||||
| Cooling Method | Natural Air Cooling | Natural Air Cooling | Natural Air Cooling | Natural Air Cooling | Forced Air Cooling | Forced Air Cooling | Forced Air Cooling | Forced Air Cooling | Forced Air Cooling | Forced Air Cooling | |
| Dimensions (W×H mm) | 68×128 | 68×128 | 72×142 | 72×142 | 87×157 | 87×157 | 109×207 | 109×207 | 130×250 | 175×300 | |
| Dimensions (D mm) | 96 | 110 | 143 | 143 | 152 | 154 | 185 | 185 | 192 | 192 |
Three-phase 460V
With Built-in EMC Filter
| Frame | B | B | C | C | C | D | D | E | E | F | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Applicable Motor Power (kW) | 0.4 | 0.75 | 1.5 | 2.2 | 3.7/4 | 5.5 | 7.5 | 11 | 15 | 18.5,22 | |
| Applicable Motor Power (HP) | 1/2 | 1 | 2 | 3 | 5 | 7.5 | 10 | 15 | 20 | 25,30 | |
| Output – Heavy Load | Rated Output Current (A) | 1.5 | 2.7 | 4.2 | 5.5 | 9 | 13 | 17 | 25 | 32 | 38,45 |
| Output – Normal Load | Rated Output Current (A) | 1.8 | 3 | 4.6 | 6.5 | 10.5 | 15.7 | 20.5 | 28 | 36 | 41.5,49 |
| Carrier Frequency (kHz) | 2–15kHz (Preset: 4kHz) | ||||||||||
| Brake Chopper | Incorporato | ||||||||||
| DC Reactor | Optional | ||||||||||
| AC Reactor | Optional | ||||||||||
| Cooling Method | Forced Air Cooling | Forced Air Cooling | Forced Air Cooling | Forced Air Cooling | Forced Air Cooling | Forced Air Cooling | Forced Air Cooling | Forced Air Cooling | Forced Air Cooling | Forced Air Cooling | |
| Dimensions (W×H mm) | 72×142 | 72×142 | 87×157 | 87×157 | 87×157 | 109×207 | 109×207 | 130×250 | 130×250 | 175×300 | |
| Dimensions (D mm) | 159 | 159 | 179 | 179 | 179 | 187 | 187 | 219 | 219 | 244 |
Without Built-in EMC Filter
| Frame | A | B | C | D | E | F | |
|---|---|---|---|---|---|---|---|
| Cooling Method | Natural Air Cooling | Natural Air Cooling | Natural Air Cooling | Forced Air Cooling | Forced Air Cooling | Forced Air Cooling | |
| Dimensions (W×H mm) | 68×128 | 72×142 | 87×157 | 109×207 | 130×250 | 175×300 | |
| Dimensions (D mm) | 129 | 143 | 143 | 152 | 154 | 185,192 |
Domande frequenti
In qualità di azienda integrata di commercio e produzione, offriamo una gamma completa di alimentatori Delta, tra cui alimentatori switching, moduli di alimentazione industriali e alimentatori regolati in corrente continua, adatti all'automazione industriale e a varie apparecchiature elettroniche.
Sì. Forniamo soluzioni personalizzate in base alle esigenze del cliente, comprese le estensioni di tensione, potenza e funzionalità, con un supporto tecnico professionale per garantire la fattibilità.
Spediamo tramite servizi logistici e di corriere affidabili, offrendo una tracciabilità completa per garantire che i prodotti raggiungano i clienti in modo sicuro e puntuale.
Il processo è semplice: selezionare il modello → presentare i requisiti → confermare la soluzione → organizzare il pagamento → consegna e guida tecnica. Forniamo un'assistenza completa per garantire che ogni fase sia completata senza problemi.
Forniamo la garanzia del produttore originale, la fornitura di parti di ricambio, la guida al funzionamento, la manutenzione e i servizi di risoluzione dei problemi per garantire che gli alimentatori Delta funzionino in modo stabile e affidabile.